Lead in Water Tests – Grade School & HS Gym Building

The Corbett School District continues to test for lead in water as part of the Oregon Department of Education’s Healthy and Safe Schools program.  Results have been received from Edge Analytical for the grade school and high school gym building, and are posted in summary form below.  As results for the retested samples are received they will be shared with the community. 

Full copies of the reports are available in the district office or by clicking on the building names below:

Action needs to be taken for tests resulting in levels at 15ppb or higher.

Water Testing Results – Grade School
Action Level is 15 parts per billion (ppb)
Fixture Location DescriptionFixture ID #Test DateTest Results (ppb)
GS Gym Coaches Sink21860100-001BF5/6/20211.2
GS Gym Shower21860100-002SH5/6/20212
GS Gym Hallway Drinking Fountain21860100-003DW5/6/2021ND
GS Gym Hallway Bottle Filler Fountain21860100-004WB5/6/2021ND
GS Gym Boys Room Sink21860100-005BF5/6/20214
GS Gym Girls Room Sink21860100-006BF5/6/20211.7
East End Boys Room Sink21860100-007BF5/6/2021ND
East End Girls Room Sink21860100-008BF5/6/2021ND
GS Room 16 Drinking Fountain21860100-009DW5/6/202194.6
GS Room 16 Sink21860100-010CF5/6/20211.1
GS Room 15 Drinking Fountain21860100-011DW5/6/20216.1
GS Room 15 Sink21860100-012CF5/6/20211.4
GS Room 14 Drinking Fountain21860100-013DW5/6/20215.1
GS Room 14 Sink21860100-014CF5/6/20211.4
GS Room 13 Drinking Fountain21860100-015DW5/6/202126.6
GS Room 13 Sink21860100-016CF5/6/20214.5
GS Room 12 Drinking Fountain21860100-017DW5/6/20213.1
GS Room 12 Sink21860100-018CF5/6/20211.3
GS Room 11 Drinking Fountain21860100-019DW5/6/202114.4
GS Room 11 Sink21860100-020CF5/6/20217
GS Room 10 Drinking Fountain21860100-021DW5/6/202117
GS Room 10 Sink21860100-022CF5/6/2021ND
GS Room 9 Drinking Fountain21860100-023DW5/6/2021123
GS Room 9 Sink21860100-024CF5/6/20211.00
GS Nurses Office Sink21860100-025NS5/6/20211
GS Office Rest Room Sink2186010-026BF5/6/2021ND
GS Office Rest Room Shower21860100-027SH5/6/2021176
GS Staff Room Sink21860100-028SF5/6/2021ND
GS Staff Rest Room Sink21860100-029BF5/6/2021ND
GS Paper Room Drinking Fountain21860100-030DW5/6/2021ND
GS Paper Room Sink21860100-031SF5/6/20212.9
GS Room 8 Drinking Fountain21860100-032DW5/6/202166.9
GS Room 8 Sink21860100-033CF5/6/20211
GS Room 7 Drinking Fountain21860100-034DW5/6/202136.7
GS Room 7 Sink21860100-035CF5/6/20211.3
GS Room 6 Drinking Fountain21860100-036DW5/6/20211.4
GS Room 6 Sink21860100-037CF5/6/20211.5
GS Room 5 Drinking Fountain21860100-038DW5/6/202125.6
GS Room 5 Sink21860100-039CF5/6/2021ND
GS Room 4 Drinking Fountain21860100-040DW5/6/20213.4
GS Room 4 Sink21860100-041CF5/6/20211.2
GS Room 3 Drinking Fountain21860100-042DW5/6/202116.5
GS Room 3 Sink21860100-043CF5/6/20214.9
GS Room 2 Drinking Fountain21860100-044DW5/6/20213.2
GS Room 2 Sink21860100-045CF5/6/20211
GS Room 1 Drinking Fountain21860100-046DW5/6/202116.2
GS Room 1 Sink21860100-047CF5/6/2021ND
GS West End Hallway Drinking Fountain21860100-048DW5/6/2021ND
GS West End Hallway Bottle Filler Fountain21860100-049WB5/6/2021ND
GS West End Boys Room Sink21860100-050BF5/6/2021ND
GS West End Girls Room Sink21860100-051BF5/6/2021ND
Retest
GS Room 16 Drinking Fountain21860100-009DWDisabled, warning posted, being retested.
GS Room 13 Drinking Fountain21860100-015DWDisabled, warning posted, being retested.
GS Room 11 Drinking Fountain21860100-019DWDisabled, warning posted, being retested.
GS Room 10 Drinking Fountain21860100-021DWDisabled, warning posted, being retested.
GS Room 9 Drinking Fountain21860100-023DWDisabled, warning posted, being retested.
GS Office Rest Room Shower21860100-027SHWarning posted, being retested.
GS Room 8 Drinking Fountain21860100-032DWDisabled, warning posted, being retested.
GS Room 7 Drinking Fountain21860100-034DWDisabled, warning posted, being retested.
GS Room 5 Drinking Fountain21860100-038DWDisabled, warning posted, being retested.
GS Room 3 Drinking Fountain21860100-042DWDisabled, warning posted, being retested.
GS Room 1 Drinking Fountain21860100-046DWDisabled, warning posted, being retested.
ND = Non Detect – Lead level is below the set detection limits of 1ppb
Water Testing Results – High School Gym Building
Action Level is 15 parts per billion (ppb)
Fixture Location DescriptionFixture ID #Test DateTest Results (ppb)
HS Front Gym Drinking Fountain21860105-001DW5/6/20213.2
HS Gym Girls Room Sink Left #121860105-002BF5/6/20216.4
HS Gym Girls Room Sink Right #221860105-003BF5/6/20217.3
HS Gym Boys Room Sink Right #121860105-004BF5/6/20212.5
HS Gym Boys Room Sink Left #221860105-005BF5/6/20213.7
HS Gym ADA Restroom Sink21860105-006BF5/6/2021ND
HS Gym ADA Restroom Shower21860105-007SH5/6/202112.50
HS Front Gym Concession Sink21860105-008SF5/6/202168
HS Gym Science Lab Sink21860105-009CF5/6/20215.5
HS Gym Girls Drinking Fountain Upper21860105-010DW5/6/20213.8
HS Gym Weight Room Water Bottle Filler21860105-011WB5/6/20212.4
HS Gym Girls Locker Room Drinking Fountain21860105-012DW5/6/20217.4
HS Gym Girls Locker Room Shower Head21860105-013SH5/6/2021777
HS Gym Girls Locker Room Left Sink 121860105-014BF5/6/20211.4
HS Gym Girls Locker Room Sink 221860105-015BF5/6/20218.6
HS Gym Girls Locker Room Sink 321860105-016BF5/6/20212.7
HS Gym Girls Locker Room Right Sink 421860105-017BF5/6/202112
HS Gym Girls Locker Room Coaches Sink21860105-018BF5/6/2021113
HS Gym Girls Locker Room Coaches Shower21860105-019SH5/6/20216910
HS Gym Girls Locker Room Ice Machine21860105-020IM5/6/2021ND
HS Gym Boys Locker Room Shower Head21860105-021SH5/6/2021482
HS Gym Boys Locker Room Left Sink21860105-022BF5/6/20215.5
HS Gym Boys Locker Room Right Sink21860105-023BF5/6/20217.9
HS Gym Boys Locker Room Drinking Fountain21860105-024DW5/6/20219.6
HS Gym Boys Locker Room Custodian Sink21860105-025OT5/6/20217.3
HS Gym Boys Locker Room Coaches Sink21860105-026BF5/6/202114.8
HS Gym Boys Locker Room Coaches Shower21860105-027SH5/6/202143.6
Retest
HS Front Gym Concession Sink21860105-008SFWarning posted, being retested.
HS Gym Girls Locker Room Shower Head21860105-013SHWarning posted, being retested.
HS Gym Girls Locker Room Coaches Sink21860105-018BFWarning posted, being retested.
HS Gym Girls Locker Room Coaches Shower21860105-019SHWarning posted, being retested.
HS Gym Boys Locker Room Shower Head21860105-021SHWarning posted, being retested.
HS Gym Boys Locker Room Coaches Sink21860105-026BFWarning posted, being retested.
HS Gym Boys Locker Room Coaches Shower21860105-027SHWarning posted, being retested.
ND = Non Detect – Lead level is below the set detection limits of 1ppb